Table 12. Control Board Operation - Continued
CONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTION
W1, W2 & Y/Y2
AUX HEAT
ON
5 KW
stage 1 Heat on instantly
Cool blower on aFter 3 seCond delay
10 KW
stage 1 Heat on instantly
Cool blower on aFter 3 seCond delay
stage 2 Heat on aFter 5 seConds delay
15 KW
stage 1 Heat on instantly
Cool blower on aFter 3 seCond delay
stage 2 Heat on aFter 5 seConds delay
stage 3 Heat on aFter 30 seConds delay
20 KW
stage 1 Heat on instantly
Cool blower on aFter 3 seCond delay
stage 2 Heat on aFter 5 seConds delay
stage 3 Heat on aFter 10 seConds delay
stage 4 Heat on aFter 15 seConds delay
25 KW
stage 1Heat on instantly
Cool blower on aFter 3 seCond delay
stage 2 Heat on aFter 5 seConds delay
stage 3 Heat on aFter 10 seConds delay
stage 4 Heat on aFter 15 seConds delay
stage 5 Heat on aFter 20 seConds delay
30 KW
stage 1Heat on instantly
Cool blower on aFter 3 seCond delay
stage 2 Heat on aFter 5 seConds delay
stage 3 Heat on aFter 10 seConds delay
stage 4 Heat on aFter 15 seConds delay
stage 5 Heat on aFter 20 seConds delay
stage 6 Heat on aFter 25 seConds delay
OFF
Heat stages oFF instantly
Heat blower turns oFF aFter 40 seCond delay
G
FAN
ON Fan blower on aFter 3 seCond delay
OFF Fan blower oFF instantly
Y/Y2
HEAT PUMP & COOL
ON Cool blower on aFter 3 seCond delay
OFF Cool blower oFF aFter 40 seCond delay
Y1
HEAT PUMP & COOL
ON Cool blower on aFter 3 seCond delay
OFF Cool blower oFF aFter 40 seCond delay
Y1 & Y/Y2
HEAT PUMP & COOL
ON Cool blower on aFter 3 seCond delay
OFF Cool blower oFF aFter 40 seCond delay