Kelvinator JS4BD030KB Installation Guide Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
8
Charging the Unit in AC mode at outdoor temperatures
above55°Fforoptimizedsub-coolingof10°F-12°F.
1. With the system operating at steady-state, measure the
liquid refrigerant pressure (in psig) at the outdoor unit
service valve.
2. Measure the liquid refrigerant temperature (in
Fahrenheit) at the service valve.
3. Determine the required liquid refrigerant pressure from
the appropriate charging chart (Figures 3 - 9).
• IfthepressuremeasuredinStep1isgreaterthan
the required liquid refrigerant pressure determined in
Step 3, then there is too much charge in the system.
Remove refrigerant and repeat Steps 1 through 3
until the system is correctly charged.
• IfthepressuremeasuredinStep1islessthanthe
required liquid refrigerant pressure determined in
Step 3, there is too little charge in the system. Add
refrigerant and repeat Steps 1 through 3 until the
system is correctly charged.
Application Notes for Using Charging Charts
This equipment’s cooling system contains
refrigerant under high pressure. Always use
safe and environmentally sound methods when
handling refrigerant handling or servicing the unit.
Review the factory literature and safety warnings
prior to servicing.
• Whenrepairingsystemleaks,alwaysuseanitrogen
(inert) gas to protect the refrigerant system and pressure
check the repair before re-charging. Always replace
the filter-dryers when performing any repair to the
refrigeration system with one capable of acid removal.
After completing the repairs, evacuate the system to
350 - 500 microns and weigh in the refrigerant to the
amount specified on the unit rating label.
• Chargingchartsarevalidforavarietyofindoor,return
air conditions and are most influenced by the outdoor
ambient temperature, outdoor fan operation and the
unit operating voltage. Before using these charts, make
sure the unit is in a stable operating mode. As shown
in the charging charts (Figures 3 - 9, pages 8 - 11), the
ideal system sub-cooling can vary over the range of
operation. Reference the charts to determine the ideal
amount of sub-cooling for a given liquid pressure. Units
charged to other values will not perform at the rated unit
efficiency (EER) or rated Coefficient of Performance
(COP) in heating mode.
To inspect a systems operation using quality
instruments, match the measured liquid temperature
to the units chart. The measured liquid pressure
reading should be within 3% of the charts value for
most installations.
• Forsystemsthatareoperatingwithmorethana5%
deviation, inspect the unit for the proper voltage and
phase balance and the refrigeration system for leaks.
• Unitsthatareoperatingatlessthen95%ofthenominal
voltage or with a 2% phase imbalance may see a more
significant deviation than the amount stated above.
• DO NOT use the charts in systems that have a
fan cycling under low-ambient control. Refer to the
low-ambient kit instructions for more information. (If
applicable)
250
275
300
325
350
375
400
425
450
475
500
525
550
575
600
70 75 80 85 90 95 100105 110 115 120125 130
Liquid Temperature (F)
Liquid Pressure (psig)
Remove refrigerant when above the curve
Add refrigerant when below the curve
Figure 3. Charging Chart for S4BD-018 Series (1.5 Ton Units) - TXV Matches
S4BD REFRIGERANT CHARGING CHARTS
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 19 20

Comments to this Manuals

No comments