COMFORT ALERT TROUBLESHOOTING
Table 10. LED Diagnostics
Status LED Status LED Description Status LED Troubleshooting Information
POWER
(Green LED)
Module has power Supply voltage is present at module terminals
TRIP
(Red LED)
Thermostat demand signal Y
is present, but compressor is
not running
• Compressorprotectorisopen
• Checkforhighheadpressure
• Checkcompressorsupplyvoltage
• Outdoorunitpowerdisconnectisopen
• Compressorcircuitbreakerorfuse(s)isopen
• Brokenwireorconnectorisnotmakingcontact
• Lowpressureswitchopenifpresentinsystem
• Compressorcontactorhasfailedopen
ALERT
Flash Code 1
(Yellow LED)
Long Run Time
Compressor is running
extremely long run cycles
• Lowrefrigerantcharge
• Evaporatorblowerisnotrunning
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
• Evaporatorcoilisfrozen
Check for low suction pressure
Check for excessively low thermostat setting
Check evaporator airflow (coil blockages or return airfilter)
Check ductwork or registers for blockage
• Faultymeteringdevice
CheckTXVbulbinstallation(size,locationandcontact)
Check if TXV/fixed orifice is stuck closed or defective
• Condensercoilisdirty
• Liquidlinerestriction(lterdrierblockedifpresentinsystem)
• Thermostatismalfunctioning
Solenoid plug not connected
Y2 not wired at Comfort Alert
Check thermostat sub-base or wiring for short circuit
Check thermostat installation (location, level)
• ComfortAlertfailure
ALERT
Flash Code 2
(Yellow LED)
System Pressure Trip
• Highheadpressure
Check high pressure switch if present in system
Check if system is overcharged with refrigerant
Check for non-condensable in system
Discharge or suction • Condensercoilpooraircirculation(dirty,blocked,damaged)
Pressure out of limits
• Condenserfanisnotrunning
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
Compressor overloaded
• Returnairducthassubstantialleakage
• Iflowpressureswitchpresentinsystem,checkFlashCode1information
ALERT
Flash Code 3
(Yellow LED)
Short Cycling / Compressor is
running only briefly
• Thermostatdemandsignalisintermittent
• Lowlinevoltage(contactutilityifvoltageatdisconnectislow)
• Excessiveliquidrefrigerantincompressor
• Compressorbearingsareseized
ALERT
Flash Code 4
(Yellow LED)
Locked Rotor
• Runcapacitorhasfailed
• Lowlinevoltage(contactutitlityifvoltageatdisconnectislow)
• Checkwiringconnections
• Excessiveliquidrefrigerantincompressor
• Compressorbearingsareseized
• Measurecompressoroillevel
ALERT
Flash Code 5
(Yellow LED)
Open Circuit
• Outdoorunitpowerdisconnectisopen
• Compressorcircuitbreakerorfuse(s)isopen
• Compressorcontactorhasfailedopen
Check compressor contactor wiring and connectors
Check for compressor contactor failure (burned, pitted or open)
Check wiring and connectors between supply and compressor
Check for low pilot voltage at compressor contactor coil
High pressure switch is open and requires manual reset
• Opencircuitincompressorsupplywiringorconnections
• Unusuallylongcompressorprotectorresettimeduetoextremeambienttemperature
• Compressorwindingsaredamaged
Check compressor motor winding resistance