NOTE: Do not add or remove refrigerant if pressure reading is between the curves.
Figure 4. Charging Chart for S4BD-024 Series (2 Ton Units) - TXV Matches
250
275
300
325
350
375
400
425
450
475
500
525
550
575
600
75 80 85 90 95 100 105 110115 120 125 130
Liquid Temperature (F)
Liquid Pressure (psig)
Remove refrigerant when above the curve
Add refrigerant when below the curve
135
SEE NOTE
Figure 5. Charging Chart for S4BD-030 Series (2.5 Ton Units) - TXV Matches
SEE NOTE
250
275
300
325
350
375
400
425
450
475
500
525
550
575
600
75 80 85 90 95 100 105 110115 120 125 130
Liquid Temperature (F)
Liquid Pressure (psig)
135
Add refrigerant when below the curve
Remove refrigerant when above the curve